Alert/Evac Controller Unit Description
This simple to operate controller is designed around industry standard building emergency alert/evacuate requirements. When connected to a paging system amplifier, building occupants can be alerted and/or evacuated in an orderly manner in the event of an emergency Eg: fire, gas leak, bomb scare, earthquake and so forth. Auto or manual modes of operation are selected by the front panel keyswitch.
Modes of operation:
Auto The alert tone is generated when a signal is received from the fire indicator board (FIB). After a preset time the evacuate tone is sounded unless the alert tone is manually reset. The evacuation tone continues until manually reset. When selected to auto, front panel alert and evac controls are inoperative. Other controls such as paging, bell chime and BGM function normally.
Manual In the manual position any of the functions may be initiated from the controls on the front panel, i.e. Alert, Evac, or PA.
Remote cancel function Terminals are provided for the connection of a remote cancel switch. When activated with a closing set of contacts this will cancel any activated tone, regardless of the position of the master auto/manual/isolate keyswitch on the front panel. This is particularly useful when the main equipment may not be readily accessible.
Other functions Provision has been made for a BGM source to be played through the controller. BGM is automatically muted when any other function is operated. A microphone input has been included on the front panel. This can be used for either general or emergency paging. Paging overrides all other functions. A pre-announcement chime is available on the microphone input. This can be switched on or off internally as preferred. Included is a unique tone or bell chime for signalling lunch breaks, start of class etc. This can be operated from the front panel or via contacts on the rear panel for remote activation ie. by a time clock or remote switch.
Modes of operation:
Auto The alert tone is generated when a signal is received from the fire indicator board (FIB). After a preset time the evacuate tone is sounded unless the alert tone is manually reset. The evacuation tone continues until manually reset. When selected to auto, front panel alert and evac controls are inoperative. Other controls such as paging, bell chime and BGM function normally.
Manual In the manual position any of the functions may be initiated from the controls on the front panel, i.e. Alert, Evac, or PA.
Remote cancel function Terminals are provided for the connection of a remote cancel switch. When activated with a closing set of contacts this will cancel any activated tone, regardless of the position of the master auto/manual/isolate keyswitch on the front panel. This is particularly useful when the main equipment may not be readily accessible.
Other functions Provision has been made for a BGM source to be played through the controller. BGM is automatically muted when any other function is operated. A microphone input has been included on the front panel. This can be used for either general or emergency paging. Paging overrides all other functions. A pre-announcement chime is available on the microphone input. This can be switched on or off internally as preferred. Included is a unique tone or bell chime for signalling lunch breaks, start of class etc. This can be operated from the front panel or via contacts on the rear panel for remote activation ie. by a time clock or remote switch.
| Features: |
| 1U 19" rack mount Interfaces with fire indicator boards Remote operation of alert and evac tones 240V mains and 24V DC operation Auto / manual / isolate 003 key switch Local operation of alert, evac, PA Provision for voice-over message Microphone socket for PA use BGM and auxiliary input Bell chime facility Switched 24V output for operating override relay on remote volume controls with alert/evac/PA signals Separate relays for alert and evac signals for external strobe light operation On-board timer for remote alert activation adjustable from 30 seconds to 7.5 min in 30 second increments Externally operated inputs are activated by switching to ground Auxiliary level output Can be used in a standard PA system 10 year warranty |
| Specifications |
| Output Level: 0dBm Distortion: 0.01% Frequency Response: 140Hz - 20kHz Signal to Noise Ratio Aux/Music Input: -90dB typically Alert/Evac/Chime: -70dB typically Input Sensitivity Mic: 2mV Balanced Aux Inputs: 300mV Unbalanced Output Connectors Audio Output: RCA Stereo Socket Switched 24V DC Out: Screw Terminals Input Connectors Mic: 5 pin XLR Aux Inputs: RCA Stereo Socket 24V DC Power: Screw Terminals 240V AC Power: IEC Chassis Socket Remote Contacts: Screw Terminals Muting: PTT Via Microphone Switch Contacts Controls Mic Input: Rear Volume BGM Input: Rear Volume Aux Input: Front Volume Tones & Chime: Rear Volume Power: On/Off Switch Mode Selection: 003 Keyswitch Alert Switch: Illuminated Switch Evac Switch: Illuminated Switch Bell / Chime Switch: Illuminated Switch Indicators: Power on LED Power Supply: 240V AC or 24V DC Current Draw: 50mA (idle), 130mA (max). Dimensions: 483W x 152D x 44H Protection: 1A Fuse Weight: 2.5 kg Colour: Black Options: A 2076 Voice Over Module * Specifications subject to change without notice.
|